1.Basic performance parameters

Parameter Description
Cooling Capacity • Unit: kW/RT (refrigeration ton, 1 RT ≈ 3.517 kW)
• Range: Small (<100 kW), Medium (100-1000 kW), Large (>1000 kW)
Coefficient of Performance(COP) • Formula: COP = Cooling capacity (kW) / Input power (kW)
• Typical value: 3.0~6.0 (depending on the model and working conditions)
Integrated Part Load Value Reflects the comprehensive energy efficiency under variable working conditions (such as IPLV ≥ 5.0)

 

2.Operating parameters

Components Parameter
Evaporator • Chilled water flow rate (m³/h): calculated based on cooling capacity and temperature difference (usually ΔT=5°C)
• Evaporation temperature: 2~10°C (direct expansion type) or 5~12°C (chilled water type)
Condenser • Cooling water flow (m³/h): depends on condensation heat and temperature difference (usually ΔT=5℃)
• Condensation temperature: 30~45℃ (air cooling or water cooling)
Compressor type Centrifugal, screw, scroll, piston compressors (each type is suitable for different cooling capacity ranges)

 

3.Electrical parameters

Parameter Description
Power Input Compressor power (kW), water pump power (kW), fan power (air-cooled model)
Voltage/Current Common voltage: 380V/50Hz (China), 460V/60Hz (Europe and America)
Start mode Star-delta starting, variable frequency soft starting, etc.

 

4.temperature and pressure

Chilled water inlet and outlet temperature Standard working conditions: 12℃ water inlet, 7℃ water outlet (ΔT=5℃)
Cooling water inlet and outlet temperature Standard working conditions: 32℃ water inlet, 37℃ water outlet (ΔT=5℃)
High/Low Pressure Determined by refrigerant type (such as R134a, R410A, R22 substitute)

 

5.Control and protect data

Type Description
control parameters Set temperature, flow, pressure difference, start and stop logic
protection function High and low pressure protection, overload protection, anti-freeze protection, oil pressure difference protection

 

6.Key data for selection

Cooling load calculation: need to consider building type, climate, use scenario.

Noise level: air-cooled units are usually 65~85 dB(A).

Size/weight: affects installation and transportation.

air-cooled unitsair-cooled unitsair-cooled units